Introduction to SIMATIC PDM And How to connect to a LR200 Radar via HART

Introduction to SIMATIC PDM And How to connect to a LR200 Radar via HART. Agenda: - Overview of PDM - Example of how to connect to a LR200 The objective of this web seminar is to give the viewer an idea of what PDM is and how to use it to communicate to

lyneth
Télécharger la présentation

Introduction to SIMATIC PDM And How to connect to a LR200 Radar via HART

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Introduction to SIMATIC PDM And How to connect to a LR200 Radar via HART Agenda: - Overview of PDM - Example of how to connect to a LR200 The objective of this web seminar is to give the viewer an idea of what PDM is and how to use it to communicate to a LR200 Radar unit via HART communications.

  2. What is PDM? • Stands for Process Device Manager A configuration tool Used for: • Commissioning field devices • Maintenance of field devices • Diagnosing field devices • Displayfield devices

  3. Now SIMATIC PDMA new, standardized approach Before PDM SIMATIC PDM for operation of all field devices and components based on EDD technology Different programs for operation of the associated field devices and components One piece of software for standardized operation of all field devices Device Descriptions (DD)

  4. DD • Proper name is EDD = Electronic Device Descriptor • Describes: • All the parameters in the device • All the interactions between parameters in the device • How to read/write those parameters over the communication bus • Describes simple methods for performing functions (ie set address, quick start etc.)

  5. Electronic Device Descriptor Language EDDL • is a standard for Hart, PROFIBUS and Foundation Fieldbus (OPEN) • Stores information as a text file, therefore it is independent on PC operating system

  6. Hand held • Communicator 275 PDM is a DD interpreter • DD = Device Description • SIMATIC • PDM • HART - Device Description • + • HART - device

  7. SIMATIC PDMVersatile communication • Communication with • PROFIBUS field devices • on PROFIBUS-DP • on PROFIBUS-PA • via PA coupler or • via PA link • HART field devices • via SIMATIC ET200M remote I/O • via SIMATIC ET200iS remote I/O • via HART modem • via HART multiplexer • Company-specific field devices • on SIPART bus • via isolated coupling to SIREC recorders

  8. CommunicationPROFIBUS PROFIBUS DP PROFIBUS PA

  9. CommunicationHART on PROFIBUS PROFIBUS DP

  10. CommunicationHART via multiplexer PROFIBUS DP

  11. M M M M CommunicationHART via HART modem PROFIBUS DP • In the workshop

  12. Communicationover Ethernet Ethernet / Fast Ethernet S7- 400 IE/PB Link PROFIBUS DP

  13. Any device with any communication on the workbench SIMATIC PDM - Connection points in the automation system Operator Station OS (e.g. Win CC) Engineering Station ES Ethernet .... .... .... S7- 400H S7- 400 S7- 300 IE/PB Link PROFIBUS DP 45.45 kBit/s PROFIBUS PA PROFIBUS DP redundant PROFIBUS DP HART multiplexer / interface DP/PA link ET 200M ET 200iS PROFIBUS PA RS232/ RS485 Possible SIMATIC PDM connection point

  14. A word about HART Protocol • Highway Addressable Remote Transducer • Based on Bell 202 Frequency shift keying to superimpose digital signal on top of a 4-20 mA signal • Open standard (www.hartcomm.org) • Designed to: • Replace 4-20 mA • Remote configuration • Remote diagnostics • Can be multi-dropped (up to 15) • Analog and digital communications • Analog is fast (continuous) • Digital is slow - 1200 bits/sec (i.e. 2-3 updates/sec)

  15. HART devices on PROFIBUS DP networks • Use a ET200M remote I/O rack • Advantages: • - Have ‘best in class’ • - Over 90% of fieldbus devices sold are HART • - This solution is part of Totally Integrated • Automation (TIA) • - PDM will work fine • - Main process variable is updated just as fast • as PROFIBUS PA • - HART can be Cheaper!

  16. HART on PROFIBUS - COSTS • PROFIBUS PA wire is 2.45 Euro/meter • HART wire is 1.42 Euro/meter

  17. HART on PROFIBUS • Installation costs can remove the Hardware savings • Some installations, HART is cheaper • Some installations, PROFIBUS PA is cheaper • Point to Remember: • YOU CAN CONNECT ANY HART DEVICE TO PROFIBUS

  18. HART Commands • HART commands are divided up into three types: • Universal commands • Common practice commands • Device specific commands • You can connect to a HART device by: • Using a ‘Generic’ DD that will give you just the Universal commands and Common practice commands but not the Device specific commands • Using a DD that has been written for the device that will give you access to all the commands

  19. PDM uses HCF Library • This means: • - PDM can connect to any HART device using a ‘Generic’ DD • - PDM can connect to any HART device using the device specific DD in the HCF Library • - PDM can connect to many devices that have • had a special DD written for it for PDM • All Siemens-Milltronics equipment that has HART can connect to PDM in all three way!

  20. HART Communicator 275 (Emerson) Does not have all the HART Library in it (Library is too big) HART Communicator 275 costs approx. 3000 Euro PDM cost approx. 400 Euro for base unit

  21. AMS software (Emerson) • Competes with PDM • Works with HART and Foundation Fieldbus • Has some nice features • However: • - AMS software not support straight use of the HCF • library • - AMS software can connect to any device but only • with Universal commands and the common practice commands. • - This is not enough to configure devices! • Device has to be made ‘AMSaware’ to use all HART commands

  22. SIMATIC PDMVariants • Stand alone • Local installation • Local connection to the field bus, service bus or electric circuit • Local database with export option in XML • Integrated into SIMATIC • Integrated in hardware project • System-wide commu-nication (routing) • Optimum integration into SIMATIC S7 /PCS 7

  23. SIMATIC PDMUser interface (1) • SIMATIC PDM has • Standardized displays and user interface • Terminology and linguistics based on DIN V 19259 and IEC 65/349/CD, and • conforms to VDI/VDA GMA 2187 • is Windows-compatible • Views of process devices • Process devices – Network view • Process devices – System view with status information • Hardware project (integrated into SIMATIC S7 /PCS 7)

  24. SIMATIC PDMUser interface (2) • Documentation • Online help and Getting Started • Status of parameter values • loaded, modified, invalid, initial value, not supported • Automatic assignment: Device – Parameter data records • User interface in • German • English • French • Spanish • Italian • Offline parameterization possible including consistency check

  25. SIMATIC PDMUser interface (3) • Parameterization / comparison • Online with offline • Device with device • Presentation of process values • Curves • Bar chart • Device diagnostics • Status • Quality • Commissioning aids • Calibration • Alignment • Adjustment • Identification • Bus scan (life list) • Device identification • HART multiplexer scan

  26. Ordering Information - PDM • Catalog sheet is on the web at www.fielddevices.com • Links to the product page on our website • Different options available: • - Integrated into PCS7 • - Routing via S7-400 • - Hart Multiplexer • Base Software Gives you: • - up to 4 tags per project (unlimited # of projects) • - communications via HART modem • - communications via RS232 • - communications via Profibus DP/PA • Siemens Internal use version (6ES7 658-3GA05-0YC0): • - only for Siemens people and distributors • - base software (100 EURO for two licenses) • - pop up with ‘For Siemens internal use only’

  27. HART Modems • RS-232 to HART Modem (7MF49971DA) • - made by MACTek • USB to HART Modem (ordered from MACTek) • MACTek can be found at www.mactekcorp.com

  28. ExampleLR200 HART connection PC HART Modem + - RB PLC HART Device If the PLC internal resistance is < 250 ohms, then RB of 250 to 350 ohms needs to be added.

  29. ExampleLR200 HART connection • Live demonstation