This report outlines the gas pressure tests conducted on the SDM cooling system for the ALICE experiment at CERN, detailing pressure conditions and thermal measurements. Conducted by Claudio Bortolin, Romualdo Santoro, Rosario Turrisi, and Martin Janda, the tests on 17/10/2001 and 18/10/2001 recorded varying pressures and thermal performance. Key pressure readings included P_gas levels of 1.63 bar to 1.9 bar and total heat loads exceeding 80% under various configurations. Findings support the readiness of the ALICE setup for beam tuning.

manju
Télécharger la présentation

Gas Pressure Testing for ALICE Cooling System at CERN

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. SPD Cooling: Gas pressure tests Claudio Bortolin – CERN Romualdo Santoro – CERN Rosario Turrisi – INFN PD Martin Janda– CTU (Prague)

  2. DSF Pgastest: 17/10/2001 2- bar 150W (No interlock) 1.5 bar - 100 W (interlock)

  3. DSF Pgastest: 18/10/2001

  4. P2 Pgastest: beginning Pliq= 6,1 bar – Pgas=1,63 bar Total HSs ON= 77 (Tmed = 29.6º C)

  5. P2 Pgastest: MAX HSs Pliq= 6,1 bar – Pgas=1,9 bar Total HSs ON= 83 (Tmed = 32.8º C)

  6. P2 Pgastest: final condition Pliq= 6,1 bar – Pgas=1,8 bar Total HSs ON= 81 (Tmed = 31.7º C)

  7. Temperature variation ALICE Ready Pgas=1.8 bar Pgas=1.9 bar ALICE Ready ALICE Beam tuning