DP-11. “Annex B”. Main: 150 Ampere Trip, 3Ø Branches: 4 – 60 Ampere Trip, 3Ø 2 – 40 ampere Trip, 1Ø. RISER DIAGRAM. 3 - 60 mm² THHN in 50 mm PVC CP . 3 - 50 mm² THHN in 50 mm PVC CP . DP-9. Main: 125 Ampere Trip, 3Ø Branches: 5 – 40 Ampere Trip, 1Ø
E N D
DP-11 “Annex B” Main: 150 Ampere Trip, 3Ø Branches: 4 – 60 Ampere Trip, 3Ø 2 – 40 ampere Trip, 1Ø RISER DIAGRAM 3 - 60 mm² THHN in 50 mm PVC CP 3 - 50 mm² THHN in 50 mm PVC CP DP-9 Main: 125 Ampere Trip, 3Ø Branches: 5 – 40 Ampere Trip, 1Ø 5 – 30 Ampere Trip, 1Ø 3 - 50 mm² THHN in 50 mm PVC CP DP-5 Main: 125 Ampere Trip, 3Ø Branches: 5 – 40 Ampere Trip, 1Ø 5 – 30 Ampere Trip, 1Ø Main: 125 Ampere Trip, 3Ø Branches: 2 – 60 Ampere Trip, 3Ø 4 – 40 Ampere Trip, 1Ø Main: 200 Ampere Trip, 3Ø Branches: 6 – 60 Ampere Trip, 3Ø 2 – 40 Ampere Trip, 1Ø 3 - 50 mm² THHN in 50 mm PVC CP DP-2B DP-2A 3 - 100 mm² THHN in 65 mm PVC CP 3 sets of 3 - 250 mm² THHN To 1200 AT CB Main: 800 Ampere Trip, 3Ø Branches: 1 – 200 Ampere Trip, 3Ø 1 – 150 Ampere Trip, 3Ø 3 – 125 Ampere Trip, 3Ø 3 – 100 ampere Trip, 3Ø MDP Certified correct: Approved by: Prepared by: SUPPLY AND INSTALLATION OF PANEL BOARDS AND FEEDERS FOR THE ELECTRICAL LOAD GROWTH AT BIR-NOB GEALDINA E. REYES Assistant Commissioner Administrative Service RODOLFO D. AURENCIO Chief, Building & Facilities Maintenance Section BOBBY U. LABAJO Chief, General Services Div.