1 / 16

HALON

HALON. Halogen based vapourising liquids. HALON 1301 Bromotrichloromethane CF3Br. General description. Halogenated hydrocarbon derived from such as methane and ethane – good extinguishing agents Example: Carbon tetrachloride (CTC) 1.1.1 trichloroethane (methyl chloroform) Bromomethane (CB)

ray
Télécharger la présentation

HALON

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. HALON Halogen based vapourising liquids

  2. HALON1301 Bromotrichloromethane CF3Br

  3. General description • Halogenated hydrocarbon derived from such as methane and ethane – good extinguishing agents • Example: • Carbon tetrachloride (CTC) • 1.1.1 trichloroethane (methyl chloroform) • Bromomethane (CB) • Bromochlorodifluoromethane (BDF / 1211) • Bromotrifluoromethane (BTM / 1301) • All are toxic, decomposed when contact with fire – produced acid gas with chlorine, bromine or fluorine

  4. General description (cont/..) • Due to this reason, authorities reluctant to accept • However, BCF & BTM less toxic, accept for marine use

  5. Halon numbering system • 1st no – number of carbon atoms • 2nd no – number of fluorine atoms • 3rd no – number of chlorine atoms • 4th no – number of bromine atoms • 5th no – number of iodine atoms If only 4 numbers available such as 1301, meaning?

  6. Effect of component gases • Bromine • Chain breaker • Bad for ozone • 1500x worst than fluorine • Fluorine – increase its inertness and stability • Bromine – increase its fire extinguishing effectiveness

  7. Physical properties • Colourless & odourless gas • Non-corrosive in gas state, highly corrosive when dissolved in water • Used nitrogen for pressurised – 42 bar at 20°C • Process – disrupts the chain reaction of combustion - extinguish fires

  8. Toxicity • Safest agent - comparing toxicity level • Concentrations up to: • 7% can breathed 5 minutes without effect • 10% reduced to 1 minute • Temperature above 510°C – halon will decompose • Important products – Hydrogen Bromide (HBr) & Hydrogen Fluoride (HF) • Small concentrations – cause irritant, give forewarn to personnel of increasing concentrations • Considered lesser threat than other products of fire poisonous smoke - carbon monoxide etc.

  9. Required concentration • 4.25 to 5% by volume

  10. Advantages • Clean with no residue • Only slightly toxic / irritant • Easy and safe to store • Electrically non-conductive • Good penetration • Suited to automatic release • Low working concentrations – relatively safe for personnel • Fast action / response / extinguish quickly • Smaller quantity than CO2 needed – enclosed spaces • Slightly pressurised storage container / keep low pressure in liquid form • Negative catalyst

  11. Disadvantages • Toxic gas produced when contact with fire • Expensive • Limited world recharging facilities • Require propellant gas for quick release

  12. Regulations • Only permitted machinery space, pump rooms or cargo spaces solely for carriage of vehicles not carrying cargo • No new installations • System designed – minimum medium quantity discharged to space based on liquid phase within 20s • Means of safely checking pressures

  13. Regulations (cont/…) • Volume 0.16m³/Kg • Fire resistant release mechanism • Over pressure device fitted • Leakage warning alarm • For locally operated devices the concentration should not above 7% for 1301 and 5.5% for 1211 at 20°C • Discharge time for liquid phase < 10s

  14. Montreal convention • Following the Montreal protocol, the usage of Halons was agreed to be: • halved by the year 1995 • phased out by the year 2000

  15. Response / plan by IMO • No new installations after July 1992 • Testing of systems banned by January 1992, integrity test on spaces required • Requirement for Halon stocks to be recorded • Existing Halon systems phased out by 2000

  16. 2nd requirement – Halon should only used as fire fighting medium in space where no other suitable means of extinguishing the fire to protect personnel and property • This guideline is valid until January 2000 • Companies required to replace with suitable alternative - difficulty in restocking Halon as production of Halons is phased out by industry • Have suitable alternative method fitted at owners best interest. • To replace the system at convenience rather than as necessary • Halon systems still in use as of August 2000