An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. PRESENTATION ON MPT ICS SYSTEM

  2. Integrated Control System • At our MPT site there is a large installation of ICS system. • ICS consists of the following systems, • PCS (Process Control System) • ESD (Emergency Shutdown System) • FGS (Fire and Gas System) • RTU (Remote Terminal Units) For Well Pads

  3. Integrated Control System • SYSTEMS USED AT OUR SITE • PCS - Yokogawa CS3000 • ESD – Yokogawa Prosafe Rs • FGS – Yokogawa Prosafe RS • RTU – Yokogawa Stardom PLC • CONNECTIVITY – Cisco Multi Layer Switch

  4. Integrated Control System • SYSTEM DOMAIN DISTIBUTION AT OUR SITE • DOMAIN 1 – OIL AND GAS AREA / UTILITY / WELLADS • DOMAIN 2 – RGT • DOMAIN 3 – BOILERS and EPC 2 • DOMAIN 4 – BHAGYAM • DOMAIN 5 – AISHWARYA and EPC 1 & 3

  5. Integrated Control System • WHAT IS DOMAIN A Domain is typically a project, consisting of : • Field control stations • Operator stations • Engineering Stations • Marshalling Panels

  6. Integrated Control System • SYSTEM IN DOMAIN 1 • PCS – 8 Nos. • ESD – 25 Nos. ( 6 for MPT and 19 for Wellpads) • F&G – 4 Nos. • SIOS – 2 Nos. ( For RTU Connectivity with Wellpads) • Operator Stations – 14 Nos. • PCS Engg. Station – 1 Nos. • ESD and F&G Engg. Station – 1 Nos. • SOE – 1 Nos. (Sequence of events viewer) • PRMS – 1 Nos. (Process Recourse Management Server) • RMS – 1 Nos. (Remote monitoring station) • OPC – 2 Nos. ( For Data Transfer to Midstream and DOF)

  7. Integrated Control System • SYSTEM IN DOMAIN 3 • PCS – 2 Nos. • ESD – 5 Nos. • PCS Engg. Station – 1 Nos. • ESD Engg. Station – 1 Nos. • ALL THE SYSTEMS ARE LOCATED IN SS1A, SS4A, Wellpads and the final data is coming to CCR for Operation and Monitoring through redundant communication Vnet bus.

  8. System Architecture for ICS System at CCR Vnet Cable Bus 1 Bus 2 FGS PCS ESD RTU Connection Vnet Connection

  9. System Architecture for SS1A Connected to CCB

  10. System Architecture for SS4A Connected to CCB

  11. System Architecture for individual WP – ESD/FGS

  12. System Architecture for individual WP – RTU

  13. System Architecture for Cluster A & B – ESD/FGS

  14. System Architecture for Cluster A & B – RTU

  15. System Architecture for Cluster C & D - RTU

  16. System Architecture for Cluster C & D – ESD/FGS

  17. Statistics for Cabinets

  18. Statistics for Cabinets

  19. Statistics for ICS Stations and I/O • In CS3000 system, in one domain, maximum of 64 stations can be connected. At MPT, approx 60 stations have been used. Still there is a provision for 4 more stations in the existing domain. • Total I/O Counts: • for MPT – approx. 9800, • Well Pad – approx. 7000.

  20. Integrated Control System Loop Primary measuring Instruments Transmitters/ Flow meters /Analyzers etc. PCS Measurement/Auto control/Manual Control Measured Values to Controller Controller Output to Field Final Control Instruments Valves / Dampers / Motors etc.

  21. ICS Input and Output signal flow Field Inputs Field Junction Box Control Room Marshaling Panel Signal Conditioning Cards PCS Input Cards PCS Controller Control Room Marshaling Panel Signal Conditioning Cards PCS Output Cards Field Junction Box Field Outputs

  22. Integrated Control System Redundancy • REDUNDANCY IN THE SYSTEM AT OUR SITE • Communication redundancy: through two communication bus Vnet BUS 1 and Vnet Bus 2. • Control redundancy: through redundant Input and out put cards and redundant processers. • Power Supply redundancy: through redundant UPS 230 Vac power supply for all the controllers.

  23. Integrated Control System Maintenance • Maintenance activities for ICS System • Daily checking of the system status and card healthiness through system status display and system alarms. • Checking of Communication for Wellpads through IP ping. • Temperature and Humidity checking for all the panel rooms and control rooms. • Every quarter system routine checking with vendor support as part of AMC and annual shut down maintenance for the system if shutdown is provided .

  24. Integrated Control System Spares • Spares for ICS System • We are maintaining important cards for system in our stock. • We have contract with vendor for keeping spares at our site and billing for the spares would be done if they are consumed. • Emergency services for ICS system • We have contract for 24 hour telephonic support and provision for service engineer visit at out site within 24 hours in case of emergency.

  25. Integrated Control System QUESTIONS

  26. Integrated Control System THANK YOU