1 / 17

CIMExcel Software Inc. Slide 1

Flotation Cell Levels – Nonlinear Model Reference Modal Control. CIMExcel Software Inc. Slide 1. Flotation Cell Levels - Nonlinear Model Reference Modal Control. Q air 1. L 1. Q air i. ρ 1. U 1. L i. Q air n. Q in. V 1. ρ i. S in. U i. z 1. L n. V i. ρ n. U n. z i. V n.

tirza
Télécharger la présentation

CIMExcel Software Inc. Slide 1

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Flotation Cell Levels – Nonlinear Model Reference Modal Control CIMExcel Software Inc. Slide 1

  2. Flotation Cell Levels - Nonlinear Model Reference Modal Control Qair 1 L1 Qair i ρ1 U1 Li Qair n Qin V1 ρi Sin Ui z1 Ln Vi ρn Un zi Vn • note, hysteresis (backlash) is included • Vi = valve position • Ui = valve positioner CIMExcel Software Inc. Slide 2

  3. Flotation Cell Levels - Nonlinear Model Reference Modal Control Qslurry in Feedforward Leveli Qair i valve position Vj actuator positioner Uj • Level Setpoints • Operator Fixed • Feed Dependent • Startup/Shutdown + + Hysteresis Compensator + ÷ PI fi-1() - Li Solidsin Dynamic Observer Leveli Qair i CIMExcel Software Inc. Slide 3

  4. Flotation Cell Levels - Nonlinear Model Reference Modal Control • operator cell level setpoint changes time scale: 10 minutes per division, 100 minutes CIMExcel Software Inc. Slide 4

  5. Flotation Cell Levels - Nonlinear Model Reference Modal Control • feed flow dependent cell level setpoint mode time scale: 10 minutes per division, 100 minutes CIMExcel Software Inc. Slide 5

  6. Flotation Cell Levels - Nonlinear Model Reference Modal Control • froth pushup mode time scale: 10 minutes per division, 100 minutes CIMExcel Software Inc. Slide 6

  7. Flotation Cell Levels - Nonlinear Model Reference Modal Control • shutdown – startup mode time scale: 10 minutes per division, 100 minutes CIMExcel Software Inc. Slide 7

  8. Flotation Cell Levels - Nonlinear Model Reference Modal Control • excellent cell level control during variable feed flow, solids, and air flow time scale: 10 minutes per division, 100 minutes CIMExcel Software Inc. Slide 8

  9. Flotation Cell Level Dynamics • d/dt V1 = A1 d/dt L1 = d/dt Va1 + d/dt Vp1 • A1 d/dt L1 = d/dt Va1 + Qin - Q1out • = d/dt Va1 + Qin - α1 f1(V1)(ρ1L1 + ρ1z1 - ρ2L2 )0.5 • Ai d/dt Li = d/dt Vai + Qi-1out - Qiout • = d/dt Vai + αi-1 fi-1(Vi-1)(ρi-1Li-1 + ρi-1zi-1 - ρiLi )0.5 - αi fi(Vi)(ρiLi + ρizi - ρi+1Li+1 )0.5 • An d/dt Ln = d/dt Van + Qn-1out - Qnout • = d/dt Van + αn-1 fn-1(Vn-1)(ρn-1Ln-1 + ρn-1zn-1 - ρnLn )0.5 - αn fn(Vn)(ρnLn )0.5 • α1 , αi , αn constants. • L1 , Li , Ln from bottom of tank. • z1 = tank 1 – tank 2 elevations. zi = tank i - tank i+1 elevations. zn = 0. • Q1out = Qin + d/dt Va1 - A1 d/dt L1 • = α1 f1(V1)(ρ1L1 + ρ1z1 - ρ2L2 )0.5 • Q2out = Q1out + d/dt Va2 - A2 d/dt L2 = Qin + d/dt Va1 + d/dt Va2 - A1 d/dt L1 - A2 d/dt L2 • Qiout = Qin + ∑j=1i (d/dt Vaj - Aj d/dt Lj) • = αi fi(Vi)(ρiLi + ρizi - ρi+1Li+1 )0.5 • Qnout = Qin + ∑j=1n (d/dt Vaj - Aj d/dt Lj) • = αn fn(Vn)(ρnLn )0.5 CIMExcel Software Inc. Slide 9

  10. Flotation Cell Level Dynamics • solids: • τs1 d/dt S1 = Sin - S1 • τsi d/dt Si = Si-1 - Si • τsn d/dt Sn = Sn-1 - Sn • solids time constant: • τs1 = ρ1 V1 / ρin Qin • τsi = ρi Vi / ρs i-1 Qi-1 • τsn = ρn Vn / ρs n-1 Qn-1 • slurry density from solids: • ρs1 = ρore/ ( S1 + (ρore/ρwater)(1 - S1) ) • Ρs i = ρore/ ( Si + (ρore/ρwater)(1 - Si) ) • ρsn = ρore/ ( Sn + (ρore/ρwater)(1 - Sn) ) • cell density: • ρ1 = ρs1(1 - f1 ) • ρi = ρsi(1 - fi ) • ρn = ρsn(1 - fn ) CIMExcel Software Inc. Slide 10

  11. Flotation Cell Level Dynamics • cell air: • f = void fraction • τar i = cell average rise time (s) • affi = cell averaged void fraction - air flow factor • 0.5τar 1 d/dt f1 = aff1 Qain1 - f1 • 0.5τar i d/dt fi = affi Qain i - fi • 0.5τar n d/dt fn = affn Qain n - fn • Vai = Vi fi= Ai Li fi • d/dt Va1 = 2A1 L1 (aff1Qain1 - f1) / τar 1 • d/dt Vai = 2Ai Li (affiQaini - fi) / τar i • d/dt Van = 2An Ln (affnQainn - fn) / τar n CIMExcel Software Inc. Slide 11

  12. Flotation Cell Level Dynamics – Identification Mode • valve perturbations time scale: 1 minute per division, 10 minutes CIMExcel Software Inc. Slide 12

  13. Flotation Cell Level Dynamics – Identification Mode • air valve perturbations time scale: 1 minute per division, 10 minutes CIMExcel Software Inc. Slide 13

  14. Flotation Cell Level Dynamics – Identification Mode • long term feed flow perturbations time scale: 10 minutes per division, 100 minutes CIMExcel Software Inc. Slide 14

  15. Flotation Cell Level Dynamics – Identification Mode • feed flow perturbations time scale: 10 minutes per division, 100 minutes CIMExcel Software Inc. Slide 15

  16. Flotation Cell Level Dynamics – Identification Mode • air flow perturbations time scale: 10 minutes per division, 100 minutes CIMExcel Software Inc. Slide 16

  17. Flotation Cell Level Dynamics - Identification Mode • feed solids perturbations time scale: 10 minutes per division, 100 minutes CIMExcel Software Inc. Slide 17

More Related