IFRO Testing - WECC

IFRO Testing - WECC. Summary of Results Eric H. Allen – NERC. WECC 2012-13LW2 Case. L/O 2 PV (net 2740 MW) B: 59.78 Hz C: 59.68 Hz. 60.0 -. 59.9 -. B. 1200 MW/ dHz. 59.8 -. 59.7 -. C. 59.6 -. Detuned to 840 MW/ dHz. L/O 2 PV (net 2740 MW) B: 59.68 Hz C: 59.56 Hz. 60.0 -.

trey
Télécharger la présentation

IFRO Testing - WECC

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. IFRO Testing - WECC Summary of Results Eric H. Allen – NERC

  2. WECC 2012-13LW2 Case L/O 2 PV (net 2740 MW) B: 59.78 Hz C: 59.68 Hz 60.0 - 59.9 - B 1200 MW/dHz 59.8 - 59.7 - C 59.6 -

  3. Detuned to 840 MW/dHz L/O 2 PV (net 2740 MW) B: 59.68 Hz C: 59.56 Hz 60.0 - 59.9 - 59.8 - B 59.7 - 59.6 - C

  4. NERC FRI Report • Recommended Interconnection Frequency Response Obligations (IFRO): • Eastern: 1,002 MW/dHz • Western: 840 MW/dHz • Texas: 286 MW/dHz • Quebec: 179 MW/dHz • At 840 MW/dHz, frequency in Western Interconnection is indicated to remain above UFLS threshold of 59.5 Hz following L/O 2 Palo Verde units

  5. Caveat Emptor • However, frequency behavior is dependent on the composition of the frequency response • A single MW/dHz number is insufficient to adequately characterize the frequency response in an interconnection • Some units have “squelched” (unsustained) response • Units that do respond can run out of headroom