1 / 26

STATIC ELECTRICITY AND CLEANING OF EQUIPMENT

STATIC ELECTRICITY AND CLEANING OF EQUIPMENT. Presented by: Dhairya Mehta Shamel Merchant Shashank Maindarkar Manish Medar. OVERVIEW. What is Static Electricity Major Sources in Industry Some Calculations for Spark Ignition Minimum Ignition Energy Hazard Assessment

Télécharger la présentation

STATIC ELECTRICITY AND CLEANING OF EQUIPMENT

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. STATIC ELECTRICITY AND CLEANING OF EQUIPMENT Presented by: Dhairya Mehta Shamel Merchant ShashankMaindarkar Manish Medar

  2. OVERVIEW • What is Static Electricity • Major Sources in Industry • Some Calculations for Spark Ignition • Minimum Ignition Energy • Hazard Assessment • Precautions to be taken • Case Study

  3. What is Static Electricity? • Electrical Imbalance on the surface of a material • Transfer of Electrons • Causes Spark ignition, which under favorable (?) conditions can lead to explosion

  4. Major Sources of Static in Industry • Use of Power / Conveyor belts • Pulverized materials / dusts pneumatically transported • The flow of fluids through pipes or conduits, or from orifices into tanks or containers • The flow of gases from orifices • The use of rubber-tyred vehicles

  5. Typical Numbers Charge production in typical operations for non-accumulators[C/kg]: Non-Accumulators: Conductivity < 50 pico - mhos/cm • Sieving: 10-11 - 10-9 • Pouring: 10-9 - 10-7 • Micronising: 10-7 - 10-4 • Pneumatic Transport: 10-6 - 10-4 Calculation example: • Pouring operation of 100 kg Product: (10-8 C/kg)Charge on product: 10-6 C • Spark energy: E = 0.5 x C x V C = 10-6 C; V = 10 kV (typical value for spark discharge) Then discharge energy E = 5 mJ

  6. Minimum Ignition Energy MIE the minimum energy that can ignite a mixture of a specified flammable material with air or oxygen, measured by a standard procedure Typical minimum ignition energy values for Combustible Vapors: Soot: > 4000 mJ Natural products: > 10 mJ Organic chemicals: 1-10 mJ Aluminium, Sulphur: < 1mJ Methane: 0.3 mJ Carbon disulphide: 0.068 mJ Hydrogen: 0.012 mJ

  7. Electrostatic Hazard Assessment - logic • Is there a flammable atmosphere? • Will charge be generated? • Can charge accumulate? • Is the field strength high enough to breakdown the surrounding air? • Is there sufficient energy to ignite the flammable atmosphere – discharge type? • If the answer is YES, then there is a risk of ignition!

  8. General Means of Control • Bonding and earthing of stationary conductive equipment. • Increasing the conductance of floors, footwear, wheels and tyres • Increasing the conductivity of non-conductors

  9. Fig. Filling a Tanker with a Flammable Liquid

  10. Precautions MINIMISE CHARGING Fluids • Keep Flow Velocity Low • Avoid 2nd Phase entrainment • Avoid Pumps, Filters etc. specially near vessels AVOID CHARGE ACCUMULATION Earth All Conducting Parts - e.g. plant & items • Generally <10 ohm • Special cases <106 ohm Earth Personnel MAXIMISE CHARGE DISSIPATION Liquids Increase Conductivity (e.g. ‘improver’ Stadis 450)

  11. Barton Solvents Wichita facility Case - Study • Flammable Liquid: VM & P Naphtha • Incident: While Transferring VM & P Naphtha to a storage tank, an explosion occurred. (July, 2007) • Investigated by: U.S. Chemical Safety and Hazard Investigation Board • Main Cause: Static Electricity Spark Ignition

  12. Key Findings • Tank Contained ignitable vapor-air mixture in the head space • Stop-start filling, trapping air in the transfer piping • The tank had a liquid level gauging system float with a loose linkage • The MSDS for the VM&P naphtha involved in this incident did not adequately communicate the explosive hazard.

  13. Recommendations • Add a Nonflammable, Nonreactive (inert) gas to tank head Space • Modify or Replace Loose Linkage tank level floats • Use Anti-Static Additives • Reduced flow (Pumping) Velocity

  14. CLEANING OF EQUIPMENT IN PROCESS INDUSTRIES • Main methods: • Chemical • Mechanical • Combination of chemical and mechanical

  15. Chemical cleaning to remove • Deposits build up due to: • Carbonaceous or organic structure molecules • Algae and slime organisms • Degradation deposits • Preoperational deposits

  16. CHEMICAL CLEANING SOLVENTS • Alkaline Cleaners - Degreasing of metal surface - Caustic Soda-Surfactant - Caustic Soda plus potassium permanganate (for sulfide deposits) • Organic Acids - Remove oxides, mill scale and other impurities - Monoammoniated Citric Acid Citric Ion – Chelating agent for iron (pH 3.5) • Inorganic Acids - Remove water side deposits, iron oxides and calcium scales - Inhibited Muriatic Acid (HCl), Inhibited Sulphuric Acid

  17. CHEMICAL CLEANING SOLVENTS • Organic Solvents - Removal of grease and oil spots - Spent solution might be recyclable - M-Pyrol for PVC Reactors • Complexing, chelating or sequestering agents - React with hardness ions, forming water soluble complexes - Expensive but selective complexation - Ease and safety - EDTA, gluconates and polyphosphonates

  18. Solvent Cleaning Methods • Circulation - Circulation of solvent • Cascade Method - Used for towers - Chemical pumped through reflux line and cascade down over trays and interior tower - Soils at bottom of tray –unremoved - High pumping capacity of solvents

  19. Solvent Cleaning Methods • Fill and Soak - Vessel filled with solvent and let to soak - 15 min – 1 hour - Proper flushing to remove loose soil - Vent – to remove gases produced during reaction between soil and deposit • On stream Cleaning - Steam Vapor phase cleaning – solvents introduced at high pressure, soils carried with vapor - Foam Cleaning – Foamed solvent solution to increase contact time - Foam also has characteristic property of reducing static electricity - Cost effective compared to fill and soak - Aeration reduces total weight – important when structural integrity ?

  20. Solvent Cleaning Methods • Gel Cleaning - Similar to foam cleaning - Gel type cleaning agent sprayed or brushed on surface - Remove iron oxide prior to painting - Eg. naval gel • Pickling and passivating - Agents act as corrosion inhibitors and passivators - CS use HCl, Alloy use ammoniated citric acids

  21. Mechanical Methods • Water jetting - Hyperblasting water used at 1000-10000 psi - Sheer force remove deposits - Consists of lances and specially designed nozzle - Extremely dangerous

  22. Mechanical Methods • Hydrodrilling, Plugs, Crawlers - Special drills used with water to cut through heavy deposits in tube walls - Water –Lubricant and flushing

  23. Case Studies • Xerox • 670000 pounds of emissions • Replacement of chlorinated solvents with citric acid • Reduction of emissions by 90% • Saves USD 40000/yr in hazardous waste disposal

  24. Case Studies • DuPont-Merck • Installed integrated ultrasonic transducer and rod-shaped tubular ultrasonic resonator • Eliminates the need to buy cleaning solvents and to dispose of solvent waste • Vapor emissions on site were reduced by 80% • 8 cleaning cycles to pay for the system

  25. Case Studies • Parr Paints • Installed high pressure system • Reduction in latex adhering to walls • Cost of high pressure unit, $800. • Savings in waste disposal, $3000/yr. • Payback, 1.7 months