An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Ratio Control (比值控制) Lei Xie Institute of Industrial Control, Zhejiang University, Hangzhou, P. R. China 2013/04/17

  2. Contents • Concept of Ratio Control • Design of Ratio Control Schemes • Cross-limiting Control of Air/Fuel Ratio in a Boiler or Furnace • Summary

  3. Blending of Two Liquid Streams Problem: when the flow rate of NaOH stream varies, it is required to maintain the concentration of blended liquid at 6 ~ 8% by manipulating the water flow rate. Schemes: (1) Concentration control of the blended liquid------Feedback control (2) Flow ratio control of input streams-----Feedforward control

  4. General Ratio Control Problem Problem: to manipulate the flow rate of stream A to maintain the two streams in a constant ratioQA/ QB= KAB, as the flow rate of stream B varies. Stream B often referred to as wild flow.

  5. Ratio Control Scheme #1 Suppose both of the flow transmitters are linear. Sometimes, they are nonlinear Steady-state condition:

  6. Ratio Control Scheme #2 Steady-state condition:

  7. Ratio Control Scheme #3 For DDZ-III instruments, the output of the multiplier is Steady-state condition: IA = I0

  8. Ratio Control Scheme #4 For DDZ-III instruments, the output of the Divider is Steady-state: K4 = IA / IB There are strong nonlinearity in flow loop of stream A. Why?

  9. Double Closed-loop Ratio Control Scheme Compare Ratio control Simple control

  10. Variable Ratio Control Scheme If main disturbances are from PV, RF; how can you improve control performances ? Steady-state Equation is

  11. Basic Boiler Control Problems • Design your control systems to satisfy • Safety. Level & air/fuel ratio control • Meet the need of users. Steam pressure control • effective & economic burning. Air/fuel ratio & keep air-rich

  12. Air/Fuel Ratio in a Boiler Control Scheme #1 Parallel control with manually adjusted air/fuel ratio Background Existing problem ?

  13. Air/Fuel Ratio in a Boiler Control Scheme #2 Ratio control with manually adjusted air/fuel ratio

  14. Air/Fuel Ratio in a Boiler Control Scheme #3 Ratio control with manually adjusted air/fuel ratio Which difference from Scheme #2 ? Existing problems ?

  15. Air/Fuel Ratio Control Scheme #4 Cross-limiting control (双交叉控制) with manually adjusted air/fuel ratio Explain its principle

  16. Air/Fuel Ratio in a Boiler Control Scheme #5 Cross-limiting control with O2 trim (带有O2调节的双交叉控制)

  17. Summary • Concept of Ratio Control • Design of Ratio Control Schemes • Cross-limiting Control of Air/Fuel Ratio in a Boiler or Furnace

  18. Exercise 6.1 It is required to dilute NaOH liquid with water. Assume that the transmitter span of NaOH liquid is 0 ~ 30 T/hr, the transmitter span of water flow is 0 ~ 120 T/hr, and both transmitters are linear DDZ-III instruments with 4 ~ 20 mA DC output. In addition, K is a ratio calculation unit which output satisfies (1) Obtain the functional relation of K value and flow ratio F1/F2; (2) Determine the value of K if the mass concentration of NaOH liquid is 20% and it is required to be diluted into 5% with water. (3) Obtain the change range of I2 and I3 if F1 varies in 10 ~ 20T/hr.

  19. Exercise 6.2 Problem 5-2 (p.112) in Automated Continuous Process Control. In detail, (1) Select the action of control valves (failed-open or failed-close) and determine the action of controllers (direct or reverse action); (2) Design your logical ratio control scheme and show it directly in process diagram; (3) Explain the automatic control process when we want to increase the methane required.

  20. Next Topic • Override/Constraint Control Problem • Design of Constrain Control Systems • Reset Windup and Its Prevention in Constrain Control • Selective Control Schemes