1 / 13

Short circuit loop measurement

Loop impedance meters. Short circuit loop measurement. Resistance or Impedance ?. Principle of measurement L-PE circuit. Z Loop =Z sec +Z L1 +Z PE. I psc - prospective of short circuit current U n – mains voltage (220V or 230V). Z L1 – impedance of phase lead

abie
Télécharger la présentation

Short circuit loop measurement

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Loop impedance meters Short circuit loop measurement

  2. Resistance or Impedance ?

  3. Principle of measurement L-PE circuit ZLoop=Zsec+ZL1+ZPE Ipsc- prospective of short circuit current Un – mains voltage (220V or 230V) ZL1 – impedance of phase lead Zsec – impedance of transformer secondary winding ZPE – impedance of protecting lead

  4. Loop impedance meter MZC-310S • High testing current of short-circuit loop measurement (up to 280A) with resolution 0,1 mΩ • Low testing current of short-circuit loop measurement (up to 42A)with resolution 0,01Ω • Touch voltage and shock voltage mesurement • Memory of 990 test results

  5. MZC-310S MENU Choose lenght of the leads for 2p method Choose nominal voltage Choose touche voltage or schock voltage measurement with 4 pole method

  6. LCD display Impedance „Z” Length of cables Type of method Prospective Short-Circuit Current Memory Resistance Reactance Impedance Main Result Voltage Frequency Voltage and frequency currently present on test terminals

  7. Measurement of impedance in L-PE circuit (2 pole method) Imax 42A

  8. Measurement of shock voltage UT

  9. Measurement of impedance in L-PE circuit (4 pole method) Imax 280A

  10. Measurement of impedance in L-PE circuit (4 pole method) • 4-pole method of testing a short circuit loop is specifically designed for testing installations with very low short circuit loop impedance (in sub-stations and power stations) • Other instruments while measuring short circuit loop impedance below 0.12Ω have a measurement error exceeding 30% which disturbs DIN VDE 0413 standards • Measurement range 7,2mΩ - 2Ω (1999mΩ)

  11. Measuring range

  12. MZC-200 MZC-300, MZC-303E MZC-310S

  13. Accessories