System Strength/Short Circuit Current Minimum Requirement

System Strength/Short Circuit Current Minimum Requirement. June 5, 2014. Background. In parallel with the ERCOT PREZ Study, Sharyland has been evaluating the transmission system performance in the Panhandle region, specifically:

rianne
Télécharger la présentation

System Strength/Short Circuit Current Minimum Requirement

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. System Strength/Short Circuit Current Minimum Requirement June 5, 2014

  2. Background In parallel with the ERCOT PREZ Study, Sharyland has been evaluating the transmission system performance in the Panhandle region, specifically: • Including generation resources meeting Section 6.9 of the ERCOT Planning Guides • Completed assessments for the Panhandle Region including: • steady state voltage security • transient voltage stability • system strength assessments • Issue: • The ERCOT Panhandle region does not have synchronous generators/machines or loads, which provide system strength to the grid via short circuit current ratio (SCR) • For wind generation control systems to work properly, a strong SCR is necessary • Synchronous condensers can provide improved system strength to mitigate the issues – but what should be the criteria for SCR for a bus and a region? • Criteria should apply to both Planning and Operations limits

  3. Weighted Short Circuit Ratio (WSCR) • ERCOT staff has proposed a minimum Weighted Short Circuit Ratio (WSCR) of 1.5 for the Panhandle region • WSCR would become a default minimum criteria – but not proposed as a Protocol or Planning Guide requirement • There are no known WSCR minimums elsewhere - Also important to differentiate between WSCR and the SCR requirements at the POI for turbine vendors • Sharyland utilized a Composite Short Circuit Ratio (CSCR) approach to evaluate “optimal” amount of synchronous condensers required for in the Panhandle • Both CSCR and WSCR approaches observed to yield similar results • Sharyland deems it important to investigate the “technical basis/justification” for the WSCR threshold – synchronous condenser requirements are very sensitive to the target • Using results from system strength studies performed by Sharyland, a target of 1.2 for CSCR/WSCR seems appropriate maintain control stability and 3 GW of wind exports do not require Synchronous Condensers • Using a 1.5 CSCR/WSCR requires 250 MW of Synchronous Condensers at 3 GW of wind exports

  4. Proposal for ROS Consideration • ROS to assign a working group to address the following: • Review the WSCR methodology developed by ERCOT • Determine the appropriate target/criteria for minimum POI SCR and Regional WSCR