An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. PID Controllers Jack Stankovic University of Virginia Spring 2015

  2. I Control: Integral Control PI Control: Proportional-Integral Control D Control: Derivative Control PD Control: Proportional-Derivative Control PID Control: Proportional-Integral-Derivative Control Summary Outline

  3. P Control • What is wrong with P control? • Non-zero steady-state error • Why? • When (current, instantaneous) error becomes zero then there is no longer a control signal

  4. I Control • What is I control? • The controller output is proportional to the integral of all past errors U(z) E(z) Integral Controller

  5. Integral Control Adds Pole D(z) N(z) + + Y(z) U(z) + E(z) + + T(z) R(z) KI z/ z-1 G(z) -

  6. PI Control

  7. D Control • D Control: the control output is proportional to the rate of change of the error • D control is able to make an adjustment prior to the appearance of even larger errors. • D control is never used alone, because of its zero output when the error remains constant.

  8. PD Control

  9. PID Control

  10. I Control • Mostly used with P control • Here, by itself to demonstrate its main effects • Zero steady state error • Slow response

  11. Introducing I Control • What is I control? • The controller output is proportional to the integral of all past errors U(z) E(z) Integral Controller

  12. I Control D(z) N(z) + + Y(z) U(z) + E(z) + + T(z) R(z) KI z/ z-1 G(z) -

  13. Steady-State Error with I Control • Start with Example 9.1: the IBM Lotus Domino Server Recall Here H(z) = 1

  14. Example (continued) Multiply top and bottom by (z-1) then set z = 1

  15. Why is the steady state error zero

  16. General Case for G(z) • The steady-state error of a system with I control is 0, as long as the close-loop system is stable.

  17. The steady-state error due to disturbance

  18. Example 9.3 • Disturbance Rejection in the IBM Lotus Domino Server

  19. Transient Response with I Control • I Control eliminates the steady-state error, but it slows the system down • The reason is the integrator adds an open-loop pole at 1, which generates a closed-loop pole that is usually close to 1. • Example 9.2: Closed-loop poles of the IBM Lotus Domino Server

  20. Example 9.2 (continued) • Observe the root locus • The largest closed-loop pole is always closer to the unit circle than the open-loop pole 0.43. Here there is only P control Here there is I control

  21. PI Control • Common controller • Fast response by P control • Accurate response by I control • Good combination • Another example of Pole Placement Design • Previously we did pole placement for P controller

  22. PI Control Design by Pole Placement • Slightly different than for P control (see p 305 in text/handout) • Design Goals: • Assumption: G(z) is a first-order system • A higher-order system is approximated by a first-order system (chapter 3)

  23. PI Control Design by Pole Placement • Example 9.5: Consider the IBM Lotus Domino server • Determine transfer function of system and SASO requirements Stable – poles within unit circle Accuracy – zero steady state error Note: 2 poles (one from G(z) and one from I control)

  24. PI Control Design by Pole Placement • Compute the desired closed loop poles • Construct and expand the desired characteristic polynomial )

  25. Construct the modeled characteristic polynomial

  26. Example 9.5 (continued) • Expand the modeled characteristic polynomial Set the desired equal to the modeled

  27. Example 9.5 (continued) • Solve for

  28. Example 9.5 (continued) • Then check • Poles are ( .5 + .33) and (.5 - .33) so the system is stable • = 1 so there is no steady state error

  29. Example 9.5 (continued) P control leads to quicker response I control leads to 0 steady-state error

  30. PI Control Design Using Root Locus • The new issue: • The root locus allows only one parameter to be varied • A PI controller has two parameters: • The P control gain, and the I control gain • Solution to this issue: • Determine possible locations of the PI controller’s zero, relative to other poles and zeros • For each relative location of the zero, draw the root locus • For the most promising relative locations, try a few possible exact locations • Simulate to verify the result

  31. Summary • I control adjust the control input based on the sum of the control errors • Eliminate steady-state error • Increase the settling time • D control adjust the control input based on the change in control error • Decrease settling time • Sensitive to noise • P, I and D can be used in combination • PI control, PD control, PID control

  32. Summary (continued) • Pole placement design • Find the values of control parameters based on a specification of desired closed-loop properties. • Root locus design • Observe how closed-loop poles change as controller parameters are adjusted

  33. Relationship to WSN and RTS • Consider PRR problem in WSN • Consider Miss Ratio Problem in RTS

  34. Extra Slides

  35. Example 9.4 • Moving-average filter plus I control • A moving average slows down the system responses • An I control also slows down the system response • So the combination leads to undesirable slow behavior • Example: IBM Lotus Domino server + I control + Moving-average filer

  36. Moving-average filter vs. I controller • An I controller works like a moving-average filter: • More response to sustained change in the output than a short transient disturbance • An I controller drives the steady-state error to 0, but the moving-average filter does not.

  37. PI Control

  38. PI Control Design by Pole Placement • Approaches: • Step 1: compute the desired closed-loop poles • Step 2,3,4: find the P control gain and I control gain • Step 5: Verify the result • Check that the closed-loop poles lie within the unit circle • Simulate transient response to assess if the design goals are met

  39. PI Control

  40. Steady-state Error with PI Control • PI has a zero steady-state error, in response to a step change in the reference input • It also holds for the disturbance input

  41. PI Control Design Using Root Locus • Example 9.6: PI control using root locus

  42. Example 9.6 (continue)

  43. Example 9.6 (continue) P control leads to quicker response I control leads to zero steady-state error

  44. CHR Controller Design Method

  45. CHR Controller Design Method

  46. CHR Controller Design Method • Example 9.7:

  47. Example 9.7 (continue) • No simulation is needed to verify it. Why? - Only one option in the table

  48. D Control

  49. D Control • A Real CS Example: • An IBM Lotus Domino server is used for healthy consulting. (MaxUsr, RIS) • Bird flu happens in this area. More and more people request for the service. • More and more hardware is added to the server. • So the reference point keeps increasing. • To deal with the increasing reference point, do we have better choices than P/I control? • How about setting the control output proportional to the rate of error change?

  50. D Control • D Control: the control output is proportional to the rate of change of the error • D control is able to make an adjustment prior to the appearance of even larger errors. • D control is never used alone, because of its zero output when the error remains constant. • The steady-state gain of a D control is 0.