An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Sprinkler Design FSE 221 – Fire Protection Systems Water-Based Suppression System Review

  2. Area/Density • Most sprinkler systems installed today are designed using an area and density approach.

  3. Occupancy Classification – NFPA 13 • First, the building use and building contents are analyzed to determine the level of fire hazard. • Usually buildings are classified as light hazard, ordinary hazard group 1, ordinary hazard group 2, extra hazard group 1, or extra hazard group 2.

  4. Light Hazard Occupancies – NFPA 13 A.5.2 Light hazard occupancies include occupancies having uses and conditions similar to the following: • Animal shelters • Churches • Clubs • Eaves and overhangs, if of combustible construction with no combustibles beneath • Educational • Hospitals, including animal hospitals and veterinary facilities • Institutional • Kennels • Libraries, except large stack rooms • It is not the committee’s intent to automatically equate library bookshelves with ordinary hazard occupancies or with library stacks. Typical library bookshelves of approximately 8 ft in height, containing books stored vertically on end, held in place in close association with each other, with aisles wider than 30 in. can be considered to be light hazard occupancies. Similarly, library stack areas, which are more akin to shelf storage or record storage, as defined in NFPA 232, Standard for the Protection of Records, should be considered to be ordinary hazard occupancies. • Museums • Nursing or convalescent homes • Offices, including data processing • Residential • Restaurant seating areas • Theaters and auditoriums, excluding stages and prosceniums • Unused attics

  5. Ordinary Hazard Occupancy (Group 1) A.5.3.1 Ordinary hazard occupancies (Group 1) include occupancies having uses and conditions similar to the following: • Automobile parking and showrooms • Bakeries • Beverage manufacturing • Canneries • Dairy products manufacturing and processing • Electronic plants • Glass and glass products manufacturing • Laundries • Restaurant service areas

  6. Ordinary Hazard Occupancies (Group 2) A.5.3.2 Ordinary hazard occupancies (Group 2) include occupancies having uses and conditions similar to the following: • Agricultural facilities • Barns and stables • Cereal mills • Chemical plants — ordinary • Confectionery products • Distilleries • Dry cleaners • Exterior Loading Docks • Exterior loading docks only utilized for loading and unloading should be classified as OH2. Where utilized for storage, exterior loading docks and all interior loading docks should be protected based upon the actual occupancy, the materials handled on the dock, as if the materials were actually stored in that configuration. • Feed mills • Horse stables • Leather goods manufacturing • Libraries — large stack room areas • Machine shops • Metal working • Mercantile • Paper and pulp mills • Paper process plants • Piers and wharves • Post offices • Printing and publishing • Racetrack stable/kennel areas, including those stable/kennel areas, barns, and associated buildings at state, county, and local fairgrounds • Repair garages • Resin application area • Stages • Textile manufacturing • Tire manufacturing • Tobacco products manufacturing • Wood machining • Wood product assembly

  7. Extra Hazard Occupancies (Group 1) A.5.4.1 Extra hazard occupancies (Group 1) include occupancies having uses and conditions similar to the following: • Aircraft hangars (except as governed by NFPA 409, Standard on Aircraft Hangars) • Combustible hydraulic fluid use areas • Die casting • Metal extruding • Plywood and particle board manufacturing • Printing [using inks having flash points below 100°F (38°C)] • Rubber reclaiming, compounding, drying, milling, vulcanizing • Saw mills • Textile picking, opening, blending, garnetting, or carding, combining of cotton, synthetics, wool shoddy, or burlap • Upholstering with plastic foams

  8. Extra Hazard Occupancies (Group 2) A.5.4.2 Extra hazard occupancies (Group 2) include occupancies having uses and conditions similar to the following: • Asphalt saturating • Flammable liquids spraying • Flow coating • Manufactured home or modular building assemblies (where finished enclosure is present and has combustible interiors) • Open oil quenching • Plastics processing • Solvent cleaning • Varnish and paint dipping

  9. NFPA 13FIGURE 11.2.3.1.1  Density/Area Curves • After determining the hazard classification, a design area and density can be determined by referencing tables in NFPA 13 Increasing density in millimeters per minute per square meter Increasing area in square feet Increasing area in square meter Increasing density in gallons per minute per square foot

  10. Theory – Design Area • The design area is a theoretical area of the building representing the worst case area where a fire could occur. • The design density is a measurement of how much water per square foot of floor area should be applied to the design area.

  11. Example 1 – Office Building • Classified as light hazard based on NFPA Appendix A.5.2 • The typical design area could range between 1500 square feet and 3000 square feet. • 1500 sq. ft = design density of 0.1 gallons per minute per square foot or a minimum of 150 gallons per minute applied over the 1500 square foot design area. • 3000 sq. ft = design density of 0.07 gallons per minute per square foot or a minimum of 210 gallons per minute applied over the 3000 square foot design area.

  12. Example 2 – Tire Manufacturing Facility • Classified as ordinary hazard group 2 – NFPA 13 Appendix A.5.3.2 • Typical design areas would be between 1500 square feet and 4000 square feet. • 1500 sq. ft = design density would be 0.2 gallons per minute per square foot or a minimum of 300 gallons per minute applied over the 1500 square foot design area. • 4000 sq. ft. = design density would be 0.15 gallons per minute per square foot or a minimum of 600 gallons per minute applied over the 4000 sq. foot design area.