1 / 28

Cooling system of the ATLAS Inner Detector cables/evaporative inlets

Cooling system of the ATLAS Inner Detector cables/evaporative inlets. M.Olcese (1) , M.Stodulski (1),(2) (1) CERN, (2) The H.Niewodniczanski Institute of Nuclear Physics Polish Academy of Sciences Updated and corrected version. Updates.

nwoodhouse
Télécharger la présentation

Cooling system of the ATLAS Inner Detector cables/evaporative inlets

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Cooling system of the ATLAS Inner Detector cables/evaporative inlets M.Olcese (1), M.Stodulski (1),(2) (1) CERN, (2) The H.Niewodniczanski Institute of Nuclear Physics Polish Academy of Sciences Updated and corrected version

  2. Updates • November 17, 2005 – update of rack numbers according to ATC-TB-EP-0007 update of cooling circuit numbers update of tile finger numbers (slides 4, 6, 14, 17) • December 8, 2005 – update of ID heater type 2 cables cooling(slide 14) modification of manifolds names (slides 4,6,8,10,12,14,17) added levels of supply/return lines in UX15; X1, X4, X7 (slide 19) • December 12, 2005 – update of manifolds/sub-manifolds names after agreement with TC (Irina, Kathy, Serguei) – added slides 3, 4, 5 • December 15, 2005 – correction of manifolds names – slides 3 • April 9, 2006 - added types of manifolds according to the drawing done by I.Wichrowska-Polok (CV-DC), July 19, 2005 – slides 3,4,5,6 added numbers of branches for each manifold and sub- manifold – added slides 7, 8, 9 M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  3. Updates - continuation • May 1, 2006 – distribution of SCT cooling circuits corrected according to installation lists in sectors 9 (L29, L35) and 3 (L5, L7, L11), slide 12 • June 18, 2006 – correction of ID cable cooling system according to real installation in sectors 9, 3, 1 (diameter and routing change), slide 9, 22 M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  4. Reference table for new and old names of manifolds M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  5. Reference table for new and old names of manifolds - continuation M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  6. Reference table for new and old names of manifolds - continuation M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  7. Reference table for new and old names of sub - manifolds M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  8. Number and size of branches per manifold M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  9. Number and size of branches per manifold - continuation M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  10. Number and size of branches per sub - manifold M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  11. Introduction • Assumptions: • design pressure 6 bar • temperature increase (in one circuit from manifold inwards ) < 6 [K] • pressure drop (in one circuit from manifold inwards) < 2.5 bar • each manifold equipped with 2 shut off valves • 1 flow meter/indicator • Grouping of cables: • SCT cables type 3 and 2 • TRT cables type 3 • TRT type 2 cables and PP2 boxes • Pixel cables type 3 • Pixel type 2 cables and PP2 boxes • ID heater cables type 3 • ID evaporative inlets type 3 and 2 M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  12. 1. Cooling of SCT Type 3 and 2 Cables – schematic of circuits US15 side M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  13. 1. Cooling of SCT Type 3 and 2 Cables – design parameters – obsolete M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  14. 2. Cooling of TRT Type 3 Cables – schematic of circuits US15 side M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  15. 2. Cooling of TRT Type 3 Cables – design parameters – obsolete M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  16. 3. Cooling of TRT Type 2 Cables and PP2 Boxes– schematic of circuits US15 side M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  17. 3. Cooling of TRT Type 2 Cables and PP2 Boxes– design parameters obsolete M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  18. 4. Cooling of Pixel Type 3 Cables – schematic of circuits US15 side M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  19. 4. Cooling of Pixel Type 3 Cables – design parameters M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  20. 5. Cooling of Pixel Type 2 Cables and PP2 Boxes– schematic of circuits US15 side M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  21. 5. Cooling of Pixel Type 2 Cables and PP2 Boxes– design parameters M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  22. 6. Cooling of ID Heater Type 3 Cables – schematic of circuits US15 side M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  23. 6. Cooling of ID Heater Type 3 Cables – design parameters M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  24. 6. Cooling of ID Heater Type 2 Cables – estimates M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  25. 7. Cooling of ID Evaporative Inlets type 3 and 2 – schematic of circuits US15 side M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  26. 7. Cooling of ID Evaporative Inlets type 3 and 2 – design parameters M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  27. Assignment of manifolds to cooling lines in UX15 USA side, top (X7): m1/6, m1/7, m2/3a, m2/3b, m2/4a, m2/4b, m3/3, m4/2, m5/3, m7/3 US side, top (X7): m1/2, m1/3a, m1/3b, m1/4, m1/5, m2/1a, m2/1b, m2/2a, m2/2b,m3/2, m5/2, m7/2 USA side bottom (X1): m1/8, m1/9, m2/5, m3/4, m3/5, m5/4, m5/5, m6/2, m7/4 US side middle (X4): m3/1, m4/1, m5/1, m6/1 US side, bottom (X1): m1/1, m3/6, m5/6, m7/1 C side US15 side M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

  28. Total cooling capacity 70.75 kW (4.8 kW evap.inlets) Total mass flow 14.80 kg/s (31 % overflow) Number of manifolds 39 Number of sub-manifolds 24 Volume of pipe work 1.3 m3 (detectors-PP3) M.Olcese, M.Stodulski, Cooling system of Inner Detector cables/evaporative inlets

More Related