Digital Control Systems (DCS)

Digital Control Systems (DCS). Lecture-1-2 Lead Compensation. Dr. Imtiaz Hussain Associate Professor Mehran University of Engineering & Technology Jamshoro, Pakistan email: imtiaz.hussain@faculty.muet.edu.pk URL : http://imtiazhussainkalwar.weebly.com/. 7 th Semester 14ES.

katherynj
Télécharger la présentation

Digital Control Systems (DCS)

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Digital Control Systems (DCS) Lecture-1-2 Lead Compensation Dr. Imtiaz Hussain Associate Professor Mehran University of Engineering & Technology Jamshoro, Pakistan email: imtiaz.hussain@faculty.muet.edu.pk URL :http://imtiazhussainkalwar.weebly.com/ 7th Semester 14ES Note: I do not claim any originality in these lectures. The contents of this presentation are mostly taken from the book of Ogatta, Norman Nise, Bishop and B C. Kuo and various other internet sources.

  2. Introduction • A feedback control system that provides an optimum performance without any necessary adjustment is rare. • Compensator: A compensator is an additional component or circuit that is inserted into a control system to equalize or compensate for a deficient performance. • Necessities of compensation • A system may be unsatisfactory in: • Stability. • Speed of response. • Steady-state error.

  3. Compensation via Root Locus • Performance measures in the time domain: • Peak time; • Overshoot; • Settling time for a step input; • Steady-state error for test inputs

  4. Commonly Used Compensators • Among the many kinds of compensators, widely employed compensators are the • Lead compensators • Lag compensators • Lag–Lead compensators

  5. Lead Compensation • Generally Lead compensators are represented by following transfer function • or , () , ()

  6. Lead Compensation , ()

  7. Electronic Lead Compensator • Following figure shows an electronic lead compensator using operational amplifiers.

  8. Electronic Lead Compensator • This can be represented as • Where, • Then, , ()

  9. Lead Compensation Techniques Based on the Root-Locus Approach. • The procedures for designing a lead compensator by the root-locus method may be stated as follows: • Step-1: Analyze the given system via root locus.

  10. Step-2 • From the performance specifications, determine the desired location for the dominant closed-loop poles.

  11. Step-3 • From the root-locus plot of the uncompensated system (original system), ascertain whether or not the gain adjustment alone can yield the desired closed loop poles. • If not, calculate the angle deficiency. • This angle must be contributed by the lead compensator if the new root locus is to pass through the desired locations for the dominant closed-loop poles.

  12. Step-4 • Assume the Lead Compensator to be: • Where α and T are determined from the angle deficiency. • Kcis determined from the requirement of the open-loop gain.

  13. Step-5 • If static error constants are not specified, determine the location of the pole and zero of the lead compensator so that the lead compensator will contribute the necessary angle. • If no other requirements are imposed on the system, try to make the value of α as large as possible. • A larger value of α generally results in a larger value of Kv, which is desirable. • Larger value of αwill produce a larger value of Kvand in most cases, the larger the Kv is, the better the system performance.

  14. Step-6 • Determine the value of Kc of the lead compensator from the magnitude condition.

  15. Example-1 • Consider the position control system shown in following figure. • It is desired to design an Electronic lead compensator Gc(s) so that the dominant closed poles have the damping ratio 0.5 and undamped natural frequency 3 rad/sec.

  16. Step-1 (Example-1) • Draw the root Locus plot of the given system. • The closed loop transfer function of the given system is: • The closed loop poles are

  17. Step-1 (Example-1) • Determine the characteristics of given system using root loci. • The damping ratio of the closed-loop poles is 0.158. • The undamped natural frequency of the closed-loop poles is 3.1623 rad/sec. • Because the damping ratio is small, this system will have a large overshoot in the step response and is not desirable.

  18. Step-2 (Example-1) • From the performance specifications, determine the desired location for the dominant closed-loop poles. • Desired performance Specifications are: • It is desired to have damping ratio 0.5 and undamped natural frequency 3 rad/sec.

  19. Step-2 (Example-1) • Alternatively desired location of closed loop poles can also be determined graphically • Desired ωn= 3 rad/sec • Desired damping ratio= 0.5 Desired Closed Loop Pole

  20. Step-3 (Exampl-1) • From the root-locus plot of the uncompensated system ascertain whether or not the gain adjustment alone can yield the desired closed loop poles. Desired Closed Loop Pole

  21. Step-3 (Exampl-1) • If not, calculate the angle deficiency. • To calculate the angle of deficiency apply Angle Condition at desired closed loop pole. Desired Closed Loop Pole -2 -1 -2 -1 100.8o 120o

  22. Step-3 (Exampl-1) • Alternatively angle of deficiency can be calculated as. Where are desired closed loop poles

  23. Step-4 (Exampl-1) • This angle must be contributed by the lead compensator if the new root locus is to pass through the desired locations for the dominant closed-loop poles. • Note that the solution to such a problem is not unique. There are infinitely many solutions.

  24. Step-5 (Exampl-1) Solution-1 • Solution-1 • If we choose the zero of the lead compensator at s = -1 so that it will cancel the plant pole at s =-1, then the compensator pole must be located at s =-3.

  25. Solution-1 Step-5 (Example-1) = • The pole and zero of compensator are determined as • The Value of can be determined as

  26. Solution-1 Step-6 (Example-1) • The Value of Kc can be determined using magnitude condition.

  27. Solution-1 Example-1 • Determine the circuit values • We must choose standard values of components • Let us choose

  28. Solution-1 Example-1 • Determine the circuit values • We must choose standard values of components • Let us choose

  29. Solution-1 Example-1 • Determine the circuit values • We must choose standard values of components • If we choose (not a standard value)

  30. Final Design Check Solution-1 • The open loop transfer function of the designed system then becomes • The closed loop transfer function of compensated system becomes.

  31. Final Design Check Solution-1

  32. Final Design Check Solution-1

  33. Final Design Check Solution-1 • The static velocity error constant for original system is obtained as follows. • The steady state error is then calculated as

  34. Final Design Check Solution-1 • The static velocity error constant for the compensated system can be calculated as • The steady state error is then calculated as

  35. Final Design Check Solution-1

  36. Solution-2 Step-5 (Exampl-1) • Solution-2 -2 -1 90o 49.2o -3 -2 -1

  37. Solution-2 Step-5 (Exampl-1) • Solution-2 -2 -1 90o 49.2o -3 -2 -1

  38. Solution-2 Step-5 (Exampl-1) • Solution-2 Uncompensated System Compensated System

  39. Root Locus

  40. Step Response

  41. Steady State Error

  42. Solution-3 Step-5 (Example-1) • If no other requirements are imposed on the system, try to make the value of α as large as possible. A larger value of α generally results in a larger value of Kv, which is desirable. • Procedure to obtain a largest possible value for α. • First, draw a horizontal line passing through point P, the desired location for one of the dominant closed-loop poles. This is shown as line PA in following figure. • Draw also a line connecting point P and the origin O. A P -2 O -1 -3 -2 -1

  43. Solution-3 Step-5 (Example-1) • Bisect the angle between the lines PA and PO, as shown in following figure. -2 -1 P A -3 -2 -1 O

  44. Solution-3 Step-5 (Example-1) • Draw two lines PC and PD that make angles with the the bisector PB. • The intersections of PC and PD with the negative real axis give the necessary locations for the pole and zero of the lead network. P A -2 -1 O -3 -2 -1 C B D

  45. Solution-3 Step-5 (Example-1) • The lead compensator has zero at s=–1.9432 and pole at s=–4.6458. • Thus, Gc(s) can be given as P -2 A -1 = -3 -2 -1 O B C D

  46. Solution-3 Step-5 (Example-1) = • For this compensator value of is • Also

  47. Solution-3 Step-6 (Example-1) • Determine the value of Kc of the lead compensator from the magnitude condition.

  48. Solution-3 Step-6 (Example-1) • The Kc is calculated as • Hence, the lead compensator Gc(s) just designed is given by

  49. Solution-3 Final Design Check Desired Closed Loop Pole Desired Closed Loop Pole Compensated System Uncompensated System

  50. Solution-3 Final Design Check