An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. SPD cooling Test benchPreliminary resultsCERN (Geneva) 12-01-11 Francescon Università & INFN Padova

  2. Summary • Description of the test bench experimental setup • Clean filters characterization • Masked filters tests • Pollution test

  3. Why a test bench Problems in the SPD cooling system (and related losses in detection efficiency) + Difficult theoretical evaluation of the problem = Experimental test bench

  4. The plant The ideal plant: • Exact replica of the real plant • Many measuring points (T, p, flow) along the stave and the whole plant Temporary plant: • Similar to the real plant (smaller scale) • Many measuring points • Being upgraded for larger flow Meanwhile: We use a thermosiphon plant built by the EN/CV/DC group’’

  5. Two-phase thermosiphon plant Condenser Chiller Dummy Load • Natural circulation of the Fluid (C4F10) • On the liquid phase by gravity • On the gas phase by pressure difference

  6. Test bench schema PP4 filter and pressure PP3 filter and pressure

  7. Test bench

  8. Setup characteristics • Available pressure difference (supply-return) dp= ~ 2,5 bar 2) Nominal flow ~ 3,7 g/s(without filters) 3) The sector is an exact replicaof an SPD sector from the mechanical/hydraulic point of view; The only difference is that in this case power on the sector is not generated by the detector but with a power supply (so the power can be adjusted very simply).

  9. Filters characterization Clean 60 um filter Clean 20 um filter

  10. Filters characterization N.B. This is the situation that we have now in the cavern: • 60 um filter in PP4 • 60 um filter in PP3 N.B. Dp is measured only on the secon filter (PP3). Two 60 um clean filters in series

  11. Filter Dp and flow variations with the power applied to the sector 60 um clean filter 0,5 g/s decrease 100 mbar decrease

  12. Flow variations with the power applied to the sector for different flowrate Clean 60 um filter

  13. Impedance of different filter combinations

  14. Bubbles formation °C bar Closing point Closing point

  15. Bubbles formation point on the p-h diagram Liquid Liquid+Gas T=18°C P=2,13 bar Gas

  16. Masked filters 3 different type of masked filter used (all clogged with epoxy glue): • Spot masked filter: filter clogged with 6 dot (dot diameter ~1 mm & clogged surface ~50% ) • Diffuse masked filter: filter clogged in a diffusive way (clogged surface ~50%) • Center masked filter: filter clogged in the middle part of the surface (clogged surface ~65%) Spot filter Center filter

  17. Influence of the clogging type on the flow

  18. Dp vs Flow for different clogged filters

  19. Pollution tests 4 kind of Goodfellow calibrated metal particles: • 0,4-12 um carbon vitreous powder • 20-50 um carbon vitreous powder • 80-200 um carbon vitreous powder <75 um carbon powder • <75 um carbon powder Test procedure: 1) The powder has been introduced in the pipe upstream both filters 2) Vacumm has been made downstream both filters 3) Flow and Dp across the PP3 filter has been evaluated for different flowrate and different power applied to the sector

  20. Powder sample Due to technical problems • Difficult handling of very small particles • Powder adehesion on the pipe wall and on the instruments • … the real amount of powder is ~50%. 0,4-12 um carbon vitreous powder0,25 g of powder

  21. Pollution test: 0,4-12 um After the insertion of 0,25 g (nominal) of 0,4-12 um carbon vitreous powder After the insertion 0,5 g (nominal) of powder: Valve fully open PP4=2,47 bar Dp=0,355 Flow=1,155 N.B. With clean 60 um filter and clean circuit: Valve fully open PP4=3,67 bar Dp=0,48 bar Flow=3,5 g/s With epoxy glue 50% diffuse clogged filter: Valve fully open PP4=3,665 bar Dp=0,484 Flow=3,368 g/s

  22. Pollution test: 80-200 um Stop&Start

  23. Pollution test: 20-50 um I,II and III insertion Steps

  24. Pollution test: <75 um I insertion III insertion Stepsteps

  25. Pollution test: 0,4-12 um (small amount) Stop&Start Powder insertion Stop&Start with vacuum

  26. Inserted another little amount (~ 0,05 g) of 0,4-12 um carbon powder

  27. Conclusions • Powder clogging results to be more effective than epoxy glue clogging • Powder crossing through the PP4 filter and following deposition on PP3 filter observed • Flow variation with Stop&Start observed

  28. Filter characterization

  29. Clean 20 um filter

  30. Two clean 60 um filter in series

  31. Spot clogged filter: filter clogged with 6 dot (approx. diameter 1 mm & approx. clogged surface 50% )

  32. Center clogged filter:filter clogged in the middle part of the surface (approx. clogged surface 65%)

  33. 0,4-12 um carbon vitreous powder0,25 g of powder

  34. Diffuse clogged filter:filter clogged with 6 dot (approx. diameter 1 mm & approx. clogged surface 50% )

  35. Two portions Of 0,4-12 um carbon powder inserted in the same time (0,5 g in total) PP4 [bar]

  36. 80-200 um carbon vitreous powder0,2 g inserted in different times

  37. -75 um carbon powder~ 0,15 g inserted in different times

  38. 20-50 um carbon vitreous powder~ 0,15 g inserted in different times

  39. Test with a little amount (~ 0,05 g) of 0,4-12 um carbon powder